T-B-UP / TH-B-UP

174.00 215.00  ( 174.00  excl. tax /// 208.80  incl. tax)

Our regulators for temperature, humidity, CO2 and VOC (volatile organic compounds). Every regulator is equipped with its own sensor(s) and may be used for two point regulation (with thresholds) or PI regulator. These devices may be used together with the 55×55 series of other manufacturers.

Clear
SKU: t-b-up-fr Category:

Description

KNX T-B-UP

Temperature

The KNX T-B-UP measures ambient temperature. The sensor can receive an external measured value via the bus and process it with the own data to an overall temperature (mixed value). The KNX T-B-UP offers two push buttons for changing the ambient temperature (target value).

The KNX T-B-UP provides four switching outputs with adjustable threshold values as well as additional AND and OR logic gates. The sensor has got a PI controller for heating and cooling.The integrated display shows the own value and data received from the bus (e. g. date,time). The housing is completed with a frame of the switching series installed in the building and thus merges with the interior.

More info and ETS product database

Functions and Operation

  1. Measurement of temperature
  2. Display 1-3 rows (own values or values received from the bus)
  3. 2 push buttons for changing the ambient temperature at the device.
    The step size can be adjusted from 0,1°C to 5°C.
  4. Mixed value from own measured value and external value (proportions can be set in percentage)
  5. PI controller for heating (one or two step) and cooling (one or two step)
  6. 4 switching outputs with adjustable threshold values (Threshold values can be set by parameter or via communication objects)
  7. 4 AND and 4 OR logic gates with each 4 inputs. Every switching incident as well as 8 logic inputs (in the form of communication objects) may be used as inputs for the logic gates. The output of each gate may optionally be configured as 1 bit or 2 x 8 bits
  8. Configuration is accomplished by means of the KNX software ETS

Technical Data

HousingPlastic material (partly lacquered)
Colours• White glossy (similar to RAL 9016 Traffic White)
• Aluminium matt
• Anthracite matt
• Stainless steel
• Special colours on request
MountingIn-wall (in socket Ø 60 mm, 42 mm deep)
Protection categoryIP 20
DimensionsHousing approx. 55 x 55 (W x H, mm),
mounting depth approx. 15 mm,
base plate approx. 71 x 71 (W x H, mm)
Total weightapprox. 50 g
Ambient temperatureOperation -10…+50°C, Storage -20…+60°C
Ambient air humiditymax. 95% R. H., avoid bedewing
Operating voltageKNX bus voltage
Bus currentmax. 6 mA,
max. 10 mA when programming LED is active
Data outputKNX +/- bus terminal plug
BCU typeOwn micro controller
PEI type0
Group addressesmax. 184
Allocationsmax. 184
Communication objects87
Measurement range-40…+80°C
Resolution0.1°C
Accuracy±0.5°C at +10…+50°C
±1°C at -10…+85°C
±1.5°C at -25…+150°C

Scope of Delivery

  1. Housing with display and sensor board
  2. Base plate

You will need in addition (not supplied):

  1. Socket Ø 60 mm, 42 mm deep
  2. Frame (for element 55 x 55 mm), suitable for the switching programme used in the building

Downloads

ETS file

KNX_T-UPalu_mitTraeger

KNX T-B-UP – Alu matt model

KNX_T-UPanth_mitTraeger

KNX T-B-UP – Anthracite matt model

KNX_T-UP_mitTraeger

KNX T-B-UP – White Glossy model

KNX_T-UPalu_mitTraeger

KNX T-B-UP – Stainless steel model

KNX TH-B-UP

Temperature / Humidity

The Indoor Sensor KNX TH-B-UP measures temperature and humidity and calculates the dew point. The sensor can receive external measured values via the bus and process them with the own data to an overall temperature and overall air humidity (mixed values). The KNX TH-B-UP offers two push buttons for changing the ambient temperature (target value).

The KNX TH-B-UP provides seven switching outputs with adjustable threshold values as well as additional AND and OR logic gates. The sensor has got a PI controller for heating and cooling (depending on temperature) and for ventilation (depending on air humidity) and it can emit a warning to the bus as soon as the area of optimum comfort (according to DIN 1946) is left.

The integrated display shows the own values and data received from the bus (e. g. date, time). The housing is completed with a frame of the switching series installed in the building and thus merges with the interior.

More info and ETS product database

Functions and Operation

  1. Measurement of temperature and air humidity (relative, absolute), calculation ofdew point
  2. Mixed values from own measured values and external values (proportions can be set in percentage)
  3. Display 1-3 rows (own values or values received from the bus)
  4. 2 push buttons for changing the ambient temperature at the device.
    The step size can be adjusted from 0,1°C to 5°C.
  5. PI controller for heating (one or two step) and cooling (one or two step) depending on temperature
  6. PI controller for ventilation depending on humidity: Dehumidify/humidify (one step) or dehumidify (one or two step)
  7. 7 switching outputs with adjustable threshold values (Threshold values can be set by parameter or via communication objects)
  8. 4 AND and 4 OR logic gates with each 4 inputs. Every switching incident as well as 8 logic inputs (in the form of communication objects) may be used as inputs for the logic gates. The output of each gate may optionally be configured as 1 bit or 2 x 8 bits
  9. Configuration is accomplished by means of the KNX software ETS

Technical Data

HousingPlastic material (partly lacquered)
Colours• White glossy (similar to RAL 9016 Traffic White)
• Aluminium matt
• Anthracite matt
• Stainless steel
• Special colours on request
MountingIn-wall (in socket Ø 60 mm, 42 mm deep)
Protection categoryIP 20
DimensionsHousing approx. 55 × 55 (W × H, mm),
mounting depth approx. 15 mm,
base plate approx. 71 × 71 (W × H, mm)
Total weightapprox. 50 g
Ambient temperatureOperation -10…+50°C, storage -20…+60°C
Ambient air humiditymax. 95% RH, avoid bedewing
Operating voltageKNX bus voltage
Bus currentmax. 6 mA,
max. 10 mA when programming LED is active
Data outputKNX +/- bus terminal plug
Communication objects117
Measurement range temperature-40…+100°C
Measurement range humidity0…100%

Scope of Delivery

  1. Housing with display and sensor board
  2. Base plate
  3. Data sheet with installation instruction (German or English)

You will need in addition (not supplied):

  1. Socket Ø 60 mm, 42 mm deep
  2. Frame (for element 55 x 55 mm) according to the switching programme used in the building

Downloads

ETS file

KNX_TH-B-UPalu2

KNX TH-B-UP – Alu matt model

KNX_TH-B-UPanth2

KNX TH-B-UP – Anthracite matt model

KNX_TH-B-UPweiss2

KNX TH-B-UP – White Glossy model

KNX_TH-B-UPalu2

KNX TH-B-UP – Stainless steel model

 

Additional information

Weight0.05 kg
Dimensions7 x 7 x 2 cm
Model

T-B-UP, TH-B-UP

Material

Aluminium matt / Aluminium mat / Aluminium matt, White glossy / Blanc brillant / Weiß glänzend, Anthracite matt / Anthracite mat / Anthrazit matt, Stainless steel / Acier affiné mat / Edelstahl